Skip to content
WireGaugeCharts

WIRE GAUGE CHARTS

4/0 wire in mm

Thickness: 11.68 mm diameter (0.460 inches), 107.22 mm² cross-section of solid copper.

4/0 · 11.68 mm

Specifications

Diameter
11.68 mm
Diameter (imperial)
0.460 in
Cross-section
107.22 mm²
Area (kcmil)
211.6
Copper resistance
0.049 Ω/1000 ft
Copper resistance (metric)
0.16 Ω/km
Copper weight
960.7 g/m
Ampacity (NEC 75 °C)
230 A

Nearest metric sizes

107.22 mm² does not match a standard metric cable size exactly. The closest conventional cross-sections are70 mm², 95 mm² and 120 mm²— engineers round this wire up (larger cross-section) for ampacity, or accept the raw equality for signal work.

One gauge away:3/0 · thinnerFull chart →

Frequently asked questions

Is 4/0 gauge wire thick or thin?

4/0 gauge wire is 11.68 mm in diameter. On the AWG scale a lower number means a thicker wire, so 4/0 AWG sits toward the thick end, where service and feeder wires live.

How many amps can 4/0 gauge wire carry?

NEC Table 310.16 rates 4/0 AWG copper at 230 A in the 75 °C column (see our amp chart for 60/75/90 °C ratings). Use the calculator to check voltage drop at your run length; long runs often force one size thicker.

What diameter is 4/0 wire in millimeters?

4/0 gauge wire is 11.68 mm (0.460 in) in diameter, with a solid-conductor cross-section of 107.22 mm².