American Wire Gauge chart (4/0–40 AWG)

The complete American wire gauge chart: diameter in mm and inches, cross-section, resistance and amp ratings for AWG 4/0 through 40 — all computed from the official AWG formula.

AWGDiameter (mm)Diameter (in)Area (mm²)Area (kcmil)Cu Ω/1000 ftCu Ω/kmTypical ampsCommon use
4/011.680.46107.22211.60.0490.16230
3/010.400.4185.03167.80.0620.20200
2/09.270.36567.43133.10.0780.26175
1/08.250.32553.48105.50.0980.32150
17.350.28942.4183.70.1240.41130
26.540.25833.6366.40.1560.51115
35.830.22926.6752.60.1970.65100
45.190.20421.1541.70.2480.8285
54.620.18216.7733.10.3131.03313
64.120.16213.3026.30.3951.3065
73.660.14410.5520.80.4981.63226
83.260.1288.3716.50.6282.0650
92.910.1146.6313.10.7922.60163
102.590.1025.2610.40.9993.2835
112.300.0914.178.21.2604.13118
122.050.0813.316.51.5885.2125
131.830.0722.625.22.0036.5788
141.630.0642.084.12.5258.2920
151.450.0571.653.33.18410.4565
161.290.0511.312.64.01513.1718
171.150.0451.0425.06316.6148
181.020.040.821.66.38520.9514
190.910.0360.651.38.05126.4135
200.810.0320.52110.15233.3130
210.720.0280.410.812.80242.0025
220.640.0250.330.616.14352.9621
230.570.0230.260.520.35666.7818
240.510.020.200.425.66884.2115
250.450.0180.160.332.367106.1913
260.400.0160.130.340.814133.9011
270.360.0140.100.251.466168.859
280.320.0130.080.264.897212.928
290.290.0110.060.181.834268.487
300.250.010.050.1103.190338.556
310.230.0090.040.1130.120426.905
320.200.0080.030.1164.079538.324.2
330.180.0070.030.1206.899678.803.6
340.160.0060.020260.895855.963
350.140.0060.020328.9831,079.342.5
360.130.0050.010414.8401,361.022.2
370.110.0040.010523.1041,716.221.8
380.100.0040.010659.6212,164.111.5
390.090.0040.010831.7672,728.901.2
400.080.0030.0101,048.8393,441.071

† chart.footnote.chassis ·chart.footnote.ampsLink

AWG ↔ mm² converter

Type either way — pick an AWG above, or enter a diameter / area below.

Diameter (in)
—
Area (kcmil)
—
Copper resistance (Ω/1000 ft)
—

American Wire Gauge, in plain terms

American Wire Gauge (AWG) is the size language for solid round wire in North America. The numbering runs backwards from intuition: bigger number, thinner wire. It dates to the drawing bench: each gauge number marks one pass through a wire-drawing die, so the more passes a rod endured, the thinner — and the higher-numbered — it became. Eighteen passes leave 18 AWG; forty leave 40 AWG, at just 0.079 mm.

The scale is logarithmic by construction. Each step of three gauges multiplies the cross-sectional area by about two; each step of six multiplies the diameter by about two; and each step of ten changes resistance by roughly a factor of six. Two residues of that drawing history remain: below 1 AWG the numbering switches to repeated "aught" passes — 1/0 ("one aught"), 2/0, 3/0, up to 4/0 — and beyond 4/0 the industry abandons gauges for kcmil labels (250, 350, 500 kcmil…), where each step is closer to +30% of area than a clean doubling.

What each column of the chart means

Diameter (mm, in). The outside width of the bare solid conductor. If you only know a wire's diameter, this is the fastest route back to its gauge: measure the metal, match the number, or let the converter above do it.

Cross-section (mm², kcmil). The amount of copper in a slice of the conductor — the number metric-world engineers size by. 1.5 mm² ≈ 16 AWG, 2.5 mm² ≈ 14 AWG, 4 mm² ≈ 12 AWG, 6 mm² ≈ 10 AWG. Kcmil ("thousand circular mils") is the imperial cousin, and above 4/0 the industry names big wire directly in it.

Resistance (Ω/1000 ft, Ω/km). Copper resistance at 20 °C — the column that answers "will it work at length?", because resistance scales linearly with distance. Count on ~0.4% per °C when the run sits somewhere warm; the copper wire gauge chart shows the ladder in isolation.

Amp rating. A practical current capacity where one exists: NEC Table 310.16 (75 °C column shown here — the dedicated wire gauge amp chart carries all three insulation temperatures for copper and aluminium) for building sizes, automotive free-air values for the thin rows. Insulation rating, bundling, ambient heat and local code all move the real number.

Where the sizes earn their keep

The names in the chart also form a jobs list. On the thick end, 1/0, 3/0 and 4/0 AWG appear in service entrances and feeders. 2 AWG wires inverter leads and grounds; 4 AWG is a 100 A service or RV battery bank. 6 AWG is the 55 A range/oven size and the welder lead. 8 AWG covers the 50 A water heater. Below that sit the household staples — 10 AWG for 30 A dryers and shops, 12 AWG for 20 A receptacles, 14 AWG for 15 A lighting — and then everything flexible and smart-home: 16 AWG speaker and lighting cord, 18 AWG for lamp cord and thermostats, 20 AWG hookup wire, and the craft tiers 26 AWG and 30 AWG where coil winding, jewelry weaving and delicate repair live.

Every one of these rows opens a dedicated page with the nearest metric cable sizes (e.g. "12 AWG → 3.31 mm², next standard conductor is 4 mm²") and the amps for both NEC-style and free-air ratings.

AWG to mm²: honest conversions

Converting between the two systems is where most online charts mislead, because no metric cable is an exact gauge twin. The honest approach is the one used in every row of this chart: compute the exact mm² of the gauge, then name the closest standard metric conductor and say "next larger" — never robot-match. A 12 AWG conductor is 3.31 mm², and the conventional metric pick for the same job is 4 mm²; 14 AWG is 2.08 mm² and its counterpart is 2.5 mm².

The converter above handles three lanes interchangeably: pick an AWG size, type a diameter in mm or inches, or enter an area in mm² or kcmil. It answers with all five numbers plus copper resistance — one reference instead of four mismatched lookup tables.

Copper, aluminium and plating

The chart is calibrated for copper (resistivity 10.371 Ω·cmil/ft at 20 °C). Aluminium conducts roughly 64% worse, so an aluminium conductor needs two gauge steps more copper area than its copper twin for the same job — that's why aluminium service entrances use 2/0 where a copper house entry might use 4/0, and why terminals matter so much. Copper-clad aluminium splits the difference at roughly +10% resistance and 70% of the weight. Tinned copper adds a solderable, corrosion-resistant skin popular in marine and industrial spans; silver plating keeps the skin effect tame at radio frequencies. For the material-by-material view, see the copper chart and the aluminium column of the amp chart.

Print, measure and verify

Two habits make this table trustworthy hands-on. First, when measuring a mystery wire, strip a clean inch and measure the bare metal — jackets lie. Compare your caliper measurement to the diameter column, or hold the conductor against the actual size wire gauge chart, which prints every popular gauge at exactly true scale (verify the 100 mm strip before trusting the printout). Second, remember that stranded bundles measure wider than the solid-diameter column while carrying identical copper; matching by copper area or strand class (see the stranded wire gauge chart) avoids the misread.

How we compute every number

Nothing on this page is transcribed from a supplier brochure. Diameter follows the standard AWG formula d = 0.005 in × 92^((36 − N)/39) for gauge N; area follows from the diameter; copper resistance follows from resistivity 10.371 Ω·cmil/ft at 20 °C; aluminium multiplies that by 1.64. Ampacity rows quote NEC Table 310.16 where the size carries one, and automotive free-air ratings where it does not. That is why the same number always appears on the home chart, the amp chart, the per-gauge pages and in the calculator — one formula, one source of truth, zero mismatched lookups.

Frequently asked questions

How do I convert AWG to mm?

Divide the gauge by nothing — use the scale: diameter in inches is 0.005 × 92^((36 − N)/39), and millimetres multiply that by 25.4. Or skip the math: the converter at the top of this page turns any AWG number into exact mm, mm² and kcmil. Ready examples: 12 AWG = 2.05 mm, 14 AWG = 1.63 mm, 18 AWG = 1.02 mm.

Is a bigger AWG number thicker wire?

No — the opposite. Bigger gauge number means thinner wire: 14 AWG (1.63 mm) is thicker than 20 AWG (0.81 mm). Below 1 AWG, the aught sizes 1/0 through 4/0 get progressively thicker than 1 AWG.

What is the difference between AWG and kcmil?

AWG labels the drawing passes that produced the wire; kcmil labels the cross-sectional area directly (1000 circular mils each). The industry switches from AWG to kcmil above 4/0 AWG (211.6 kcmil), where easy doubling ends.

Why does 10 AWG show different amp ratings on different sites?

Ampacity depends on insulation temperature and conditions: THHN at 90 °C is rated higher than the 75 °C column, and free-air automotive values differ again from NEC bundled ratings. Our amp chart shows the columns side by side so you can pick the rating your code requires.