Open a residential wall box and you’ll find solid wire in one piece. Open the machine room of the same house and the terminations are nearly all stranded. Same copper, same mm², two constructions that split the electrical world by where they install.
Same gauge, different body
AWG numbers describe the copper’s cross-section area, so a 12 AWG solid and a 12 AWG stranded carry the same current by definition. What differs is the outer diameter and the mechanics:
| Property | Solid | Stranded |
|---|---|---|
| Overall diameter | exact (2.05 mm for 12 AWG) | +10–25% (2.35–2.5 mm) |
| Flex life | ~3 bends before fatigue | thousands of cycles |
| Termination | best in backstab/screw | risks strand escape (use ferrules!) |
| Corrosion ingress | none (solid body) | wicking risk in wet runs |
Strand classes
Manufacturers grade stranded wire flexibility:
- Class B/C: 7–19 coarse strands, building wire stock (THHN/THWN-2 in multi-conductor cables like NM-B is actually solid, but service/feeder cables mostly stranded).
- Class G/H: hundreds of fine strands, welding cables and battery cable — “fine-strand” to electricians.
- Fine-strand Litz/film: for signal and RF, not power.
The practical effect: more, finer strands = droopier and take more abuse at the strain relief.
Terminals are the real divide
Solid wire pushes in and stays; the screw bites the whole cylinder. Stranded wire under the same set screw frays unless you:
- Crimp ferrules (bootlace ends — standard practice in EU panels),
- Use lugs lined for fine strand,
- Or tin-lightly (north-American practice disfavors fully tinning fine-strand in vibration due to cold-flow).
That is exactly why residential walls are solid and industrial panels are stranded-with-ferrules: each construction pairs with a termination culture.
Metric labels stay construction-blind
Metric countries print the total copper mm² on the jacket regardless of construction: 4 mm² solid and 4 mm² fine-strand carry the same label. US AWG does this implicitly, but the packaging “type: 12/2 SF STR” tells you it’s stranded. When replacing a fixture, match construction first, then gauge — spring-back behavior is a safety issue at the terminal.
Converting diameters
If you’re measuring a stranded mystery cable with calipers, don’t compare against solid charts — the air gaps fool you. Count strands × area per strand instead, or use the stranded wire gauge chart to break down the equivalence; the copper chart has the resistances for verification.